Model PD6100 Strain Gauge/Load Cell Meter Instruction Manual
12
NON-ISOLATED
TRANSMITTER
POWER SUPPLY
Terminals I+ & R: 24 VDC 10% . May be used to power
the 4-20 mA output or other devices
(except load cell/strain
gauge). Refer to Figure 7 on page 19 and Figure 17 on page
26.
ProVu Series (PD6100):
All models rated @ 40 mA max.
ProtEX-MAX (PD8 Series):
All models @ 25mA max.
EXTERNAL LOOP
POWER SUPPLY
35 VDC maximum
OUTPUT LOOP
RESISTANCE
Power supply Minimum Maximum
24 VDC
10 700
35 VDC (external)
100 1200
Modbus
®
RTU Serial Communications
SLAVE ID 1 – 247 (Meter address)
BAUD RATE 300 – 19,200 bps
TRANSMIT
TIME DELAY
Programmable between 0 and 199 ms
or transmitter always on for RS-422 communication
DATA 8 bit (1 start bit, 1 or 2 stop bits)
PARITY Even, Odd, or None with 1 or 2 stop bits
BYTE-TO-BYTE
TIMEOUT
0.01 – 2.54 second
TURN AROUND
DELAY
Less than 2 ms (fixed)
Note: Refer to the PROVU
®
Modbus Register Tables located at www.predig.com
for details.
COMPLIANCE INFORMATION
Safety
UL & c-UL LISTED USA & Canada
UL 508 Industrial Control Equipment
UL FILE NUMBER E160849
FRONT PANEL UL Type 4X, NEMA 4X, IP65; panel gasket provided
LOW VOLTAGE
DIRECTIVE
EN 61010-1:2010
Safety requirements for measurement, control, and
laboratory use